A direct power control of a DFIG based-WECS during symmetrical voltage dips

TitreA direct power control of a DFIG based-WECS during symmetrical voltage dips
Publication TypeJournal Article
Year of Publication2020
AuthorsMensou, S, Essadki, A, Nasser, T, B. Idrissi, B
JournalProtection and Control of Modern Power Systems
Volume5
Mots-clésAero-generator, Asynchronous generators, Backstepping, Backstepping technique, Doubly fed induction generators, DPC strategy, Electric equipment protection, Electric fault currents, Electric machine control, Electric power system control, Electric power transmission networks, Energy conversion, Lyapunov functions, Power control, Robustness (control systems), Rotorside converter (RSC), Stability and robustness, Stators, Two term control systems, Voltage dip, Wind energy conversion system, Wind power
Abstract

The Wind Energy Conversion System (WECS) based Doubly Fed Induction Generator (DFIG) has experienced a rapid development in the world, which leads to an increasing insertion of this source of energy in the electrical grids. The sudden and temporary drop of voltage at the network can affect the operation of the DFIG; the voltage dips produce high peak currents on the stator and rotor circuits, without protection, the rotor side converter (RSC) will suffer also from over-current limit, consequently, the RSC may even be destroyed and the generator be damaged. In this paper a new Direct Power Control (DPC) method was developed, in order to control the stator powers and help the operation of the aero-generator during the faults grid; by injecting the reactive power into the network to contribute to the return of voltage, and set the active power to the optimum value to suppress the high peak currents. The DPC method was designed using the nonlinear Backstepping (BS) controller associated with the Lyapunov function to ensure the stability and robustness of the system. A comparison study was undertaken to verify the robustness and effectiveness of the DPC-BS to that of the classical vector control (VC) using Proportional-Integral (PI) correctors. All were simulated under the Simulink® software. © 2020, The Author(s).

URLhttps://www.scopus.com/inward/record.uri?eid=2-s2.0-85078233240&doi=10.1186%2fs41601-019-0148-y&partnerID=40&md5=522588067926dd57f4d68f2b24a05345
DOI10.1186/s41601-019-0148-y
Revues: 

Partenaires

Localisation

Suivez-nous sur

         

    

Contactez-nous

ENSIAS

Avenue Mohammed Ben Abdallah Regragui, Madinat Al Irfane, BP 713, Agdal Rabat, Maroc

  Télécopie : (+212) 5 37 68 60 78

  Secrétariat de direction : 06 61 48 10 97

        Secrétariat général : 06 61 34 09 27

        Service des affaires financières : 06 61 44 76 79

        Service des affaires estudiantines : 06 62 77 10 17 / n.mhirich@um5s.net.ma

        CEDOC ST2I : 06 66 39 75 16

        Résidences : 06 61 82 89 77

Contacts

    

    Compteur de visiteurs:640,540
    Education - This is a contributing Drupal Theme
    Design by WeebPal.